Considering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relays

Author:
یاسر دامچی
,
جواد ساده
,
حبیب رجبی مشهدی
,
yaser damchi
,
Javad Sadeh
,
Habib Rajabi Mashhadi
Year
: 2015
Abstract: The aim of the relay coordination is that protection systems detect and isolate the

faulted part as fast and selective as possible.

On the other hand, in order to reduce the fault

clearing time, distance protection relays are usually equipped with pilot protection schemes.

Such schemes can be considered in the Di

stance and Directional Over-Current Relays

(D&DOCRs) coordination to achieve faster protection systems, while the selectivity is

maintained. Therefore, in this paper, a new formulation is presented for the relay

coordination problem considering pilot protection. In the proposed formulation, the

selectivity constraints for the primary distan

ce and backup overcurrent relays are defined

based on the fault at the end of the transmissi

on lines, rather than those at the end of the

first zone of the primary distance relay. To solve this nonlinear optimization problem, a

combination of Genetic Algorithm (GA) and Linear Programming (LP) is used as a Hybrid

Genetic Algorithm (HGA). The proposed approach

is tested on an 8-bus, the IEEE 14-bus

and the IEEE 39-bus test systems. Simulation

results indicate that considering the pilot

protection in the D&DOCRS coordination, not only obtains feasible and effective solutions

for the relay settings, but also reduces the overall operating time of the protection system.
URI: http://libsearch.um.ac.ir:80/fum/handle/fum/3352234
Keyword(s): irectional Overcurrent Relay,Distance Relay,Pilot Protection,Relay

Coordination
Collections :
  • ProfDoc
  • Show Full MetaData Hide Full MetaData
  • Statistics

    Considering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relays

Show full item record

contributor authorیاسر دامچیen
contributor authorجواد سادهen
contributor authorحبیب رجبی مشهدیen
contributor authoryaser damchifa
contributor authorJavad Sadehfa
contributor authorHabib Rajabi Mashhadifa
date accessioned2020-06-06T13:22:26Z
date available2020-06-06T13:22:26Z
date issued2015
identifier urihttp://libsearch.um.ac.ir:80/fum/handle/fum/3352234?locale-attribute=en
description abstractThe aim of the relay coordination is that protection systems detect and isolate the

faulted part as fast and selective as possible.

On the other hand, in order to reduce the fault

clearing time, distance protection relays are usually equipped with pilot protection schemes.

Such schemes can be considered in the Di

stance and Directional Over-Current Relays

(D&DOCRs) coordination to achieve faster protection systems, while the selectivity is

maintained. Therefore, in this paper, a new formulation is presented for the relay

coordination problem considering pilot protection. In the proposed formulation, the

selectivity constraints for the primary distan

ce and backup overcurrent relays are defined

based on the fault at the end of the transmissi

on lines, rather than those at the end of the

first zone of the primary distance relay. To solve this nonlinear optimization problem, a

combination of Genetic Algorithm (GA) and Linear Programming (LP) is used as a Hybrid

Genetic Algorithm (HGA). The proposed approach

is tested on an 8-bus, the IEEE 14-bus

and the IEEE 39-bus test systems. Simulation

results indicate that considering the pilot

protection in the D&DOCRS coordination, not only obtains feasible and effective solutions

for the relay settings, but also reduces the overall operating time of the protection system.
en
languageEnglish
titleConsidering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relaysen
typeJournal Paper
contenttypeExternal Fulltext
subject keywordsirectional Overcurrent Relayen
subject keywordsDistance Relayen
subject keywordsPilot Protectionen
subject keywordsRelay

Coordination
en
journal titleIranian Journal of Electrical and Electronic Engineeringfa