Show simple item record

contributor authorHamid Yaghobien
contributor authorH. Mortazavien
contributor authorکورش انصاری اغول بیکen
contributor authorحبیب رجبی مشهدیen
contributor authorHassan Khorashadi zadehen
contributor authorHossein Borzoeen
contributor authorKourosh Ansarifa
contributor authorHabib Rajabi Mashhadifa
date accessioned2020-06-06T13:16:35Z
date available2020-06-06T13:16:35Z
date issued2013
identifier urihttp://libsearch.um.ac.ir:80/fum/handle/fum/3348634?locale-attribute=en&show=full
description abstractThis contribution deals with the analysis of synchronous generator loss of excitation (LOE) protection. This paper presents a new method for detecting LOE in synchronous generator based on the variation of the magneticflux linkage in the air gap. To show the effectiveness of the proposed protection, comparisons are made with the conventional LOE protection methods by considering different generator sizes. The simulation results show that the proposed method is useful and effective to detect LOE conditions. The main advantage of this method is its speed and sensitivity.en
languageEnglish
titleStudy on application offlux linkage of synchronous generator for loss of excitation detectionen
typeJournal Paper
contenttypeExternal Fulltext
subject keywordssynchronous generatoren
subject keywordsloss of excitation protectionen
subject keywordslinkagefluxen
subject keywordssearch coilen
journal titleInternational Transactions on Electrical Energy Systemsfa
pages802-817
journal volume23
journal issue6
identifier linkhttps://profdoc.um.ac.ir/paper-abstract-1039369.html
identifier articleid1039369


Files in this item

FilesSizeFormatView

There are no files associated with this item.

This item appears in the following Collection(s)

Show simple item record