The static VAr compensator equations development for load balancing at desired power factor based on load admittance parameters and instantaneous voltage and current values
سال
: 2009
چکیده: Various methods for load balancing and power factor correction in three-wire and four-wire networks have been presented so far. In this paper, a new formulation has been developed such that the admittance of the compensator can be calculated to balance any loads irrespective of their nature (being resistive or reactive) and to obtain the requested power factor. During the process of power factor correction, the current is always balanced and therefore in addition to the reduction of power wasting, it is possible to operate with optimum power factor. In the developed equations the parameters of the compensator are presented in terms of both the load admittance and instantaneous voltage and current values. The extended equations are general and can be applied to any load in three or four-wire distribution systems. Simulation results show the validity of the developed formulation.
کلیدواژه(گان): distribution networks,power factor correction,static VAr compensators
کالکشن
:
-
آمار بازدید
The static VAr compensator equations development for load balancing at desired power factor based on load admittance parameters and instantaneous voltage and current values
Show full item record
contributor author | S. A. Farouji | en |
contributor author | E. Bakhshizadeh | en |
contributor author | R. Kazemzadeh | en |
contributor author | رضا قاضی | en |
contributor author | Reza Ghazi | fa |
date accessioned | 2020-06-06T13:59:30Z | |
date available | 2020-06-06T13:59:30Z | |
date copyright | 11/10/2009 | |
date issued | 2009 | |
identifier uri | http://libsearch.um.ac.ir:80/fum/handle/fum/3377844 | |
description abstract | Various methods for load balancing and power factor correction in three-wire and four-wire networks have been presented so far. In this paper, a new formulation has been developed such that the admittance of the compensator can be calculated to balance any loads irrespective of their nature (being resistive or reactive) and to obtain the requested power factor. During the process of power factor correction, the current is always balanced and therefore in addition to the reduction of power wasting, it is possible to operate with optimum power factor. In the developed equations the parameters of the compensator are presented in terms of both the load admittance and instantaneous voltage and current values. The extended equations are general and can be applied to any load in three or four-wire distribution systems. Simulation results show the validity of the developed formulation. | en |
language | English | |
title | The static VAr compensator equations development for load balancing at desired power factor based on load admittance parameters and instantaneous voltage and current values | en |
type | Conference Paper | |
contenttype | External Fulltext | |
subject keywords | distribution networks | en |
subject keywords | power factor correction | en |
subject keywords | static VAr compensators | en |
identifier link | https://profdoc.um.ac.ir/paper-abstract-1018499.html | |
conference title | International Conference on Electric Power and Energy Conversion Systems | en |
conference location | شارجه | fa |
identifier articleid | 1018499 |